In unit-1, the guide vane opening percentage in control room SCADA displays more value than it should have been. While generating 12 MW, guide opening had sometime reached up to 100%.
Primary Suspect
Moisture content in feedback sensor or problem in feedback circuit.
Maintenance Activity
Cleaned the feedback sensor to rule out the possibility of error due to moisture content.Checked the power supply and possible loose connection in sensor connector.Checked the signal converting resistor of the feedback sensor. It was found to be loosely connected to terminal. Then the resistor was firmly soldered and reconnected to the terminal.
Status after maintenance
The output in control room SCADA and unit 1 governor HMI shows the actual guide vane opening percentage. So, this issue is finally solved.